Incombustility |
 |
|
 |
|
 |
 |
Standard Testing |
 |
|
 |
 |
 |
 |
| |
| ALPOLIC®/fr – Summary of Fire Tests |
| Category |
Country |
Test Standard |
ALPOLIC®/frSpecimen |
Results & Classification |
| External Cladding |
United Kingdom |
|
4 mm & 6 mm |
|
| Germany |
DIN4102 Part 1 |
4 mm |
Class 0 |
| USA |
British Thermal Unit
(NFPA 259-93) |
4 mm |
Passed |
Climbing Drum Peel Test
(ASTM D1781-76) |
4 mm |
Passed |
Tunnel Test
(ASTM E-84) |
4 mm & 6 mm. |
Class A / Class1 |
| Modified ASTM E-108 |
4 mm |
Passed |
UBC 26-9& NFPA 285, ISMA Test
(Intermediate Scale Multi-story Apparatus) |
4 mm & 6 mm. |
Passed |
| Canada |
CAN/ULC-S 134-92,
Full-scale Exterior Wall Fire Test |
4 mm |
Passed |
| China |
GB8625, GB8626 & GB8627 |
4 mm |
Class B1 |
| Japan |
Heat Release Test for Non-combustible Material
(ISO 5660-1) |
4 mm & 6 mm. |
Passed |
| Roof |
USA |
Fire Test for Roof Covering
(ASTM E 108) |
4 mm |
Passed Class A |
| Fire Resistant Rating Wall |
USA |
1-hr Fire Rating and 2-hr Fire Rating
(ASTM E119) |
4 mm |
Does not impair fire resistant rating wall |
| Interior |
USA |
Interior Room Corner Test
(UBC 26-3) |
4 mm |
Passed |
| USA |
Combustion Toxicity Test, New York State Uniform Fire Prevention and Building Code |
4 mm |
Passed |
| Japan |
Heat Release Test for Non-combustible Material (ISO 5660-1 & Toxicity Gas Test) |
3 - 6 mm |
Passed. Certificate No. NE-209 |
|
Southwest Research Institute (SwRI) performs testing to determine the surface burning characteristics of building materials, products, and assemblies in accordance with standards referenced by ASTM E84, NFPA 255, UL 723, UBC 42-1, CAN 4-S102 and UL 910. To meet the demands of industrial fire testing requirements, the Institute's test program offers the following facilities and capabilities:
- 4,000-square-foot conditioned building
- State-of-the-art measurement system and computerized data processing
- Immediate tabulation and printout of results
- Nationally-recognized reports issued within days of the test
The SwRI Fire Technology Department is recognized by all national, federal state, and major local building standards organizations. Accredited by the Council of American Building Code officials (CABO), SwRI meets all criteria set by the Building Officials Conference of America (BOCA), International Conference of Building Officials (ICBO), and the Southern Building Code Congress International (SBCCI), With these accreditations, the department provides fire testing and listing, labeling, and follow-up services in accordance with National Evaluation Service Report Nos. NER-TL351 and NER-QA409. |
|
|
 |
 |
 |
|
 |
 |
Why do Aluminum Composite Materials (ACM) need to have Fire-rated core? |
 |
|
 |
|
 |
 |
(1) External cladding |
 |
|
 |
|
 |
 |
(2) Fire test for roof covering |
 |
|
 |
|
 |
 |
(3) Fire test for Interior |
 |
|
 |
 |
 |
 |
| |
| ALPOLIC®/fr passes the UBC26-3 Room Corner Test, a fire test to verify the hazardous flashover of interior finishing materials. |
| UBC26-3 Room corner |
|
 |
Heater: Gas burner or 30lb wood crib
Time: 15 min
The interior is finished with the testing material
(1) Side wall: The area close to the opening can be exempted
(2) Front wall
(3) Ceiling: It is optional |
|
|
|
|
|
|
 |
 |
 |
|
 |
 |
(4) Fire approval in Japan |
 |
|
 |
 |
 |
 |
| |
| ALPOLIC®/fr passes Japan’s new cone calorimeter test ISO5660-1, a standard fire test for building material classification. It is also approved as a non-combustible material for external cladding, roof covering and interior with Certificate Nos. NE-001 and NE-209. |
|
|
|
 |
 |
 |
|
|
|